Electrical [Input]
Model Number BCD800-12-24 BCD800-12-24
Nominal Vac (ip) 12 24
Actual (Vac) 10.5-14 10.5-28
Input Amps (Max) 60 60
Input Fuse (AGC) 40A x 2 40A x 2
Electrical [Output]
Output Nominal (op) 12 24
Output Volts (DC) 13.6 ± 0.05 27.2 ± 0.05
Charging Current Amps *60 *30
Output Crowbar Output Volts x (1.3± 1%) Output Volts x (1.3± 1%)
Output Fuses(ATC) 40A x2 40A x2
Output Ripple & Noise < 50 mV < 50 mV
Battery Banks 1 1
Stages 2 2
Battery Size (Amp Hours) 160-240 80-120
Regulation(Line & Load) < +/- 0.5% < +/- 0.5%
Duty Cycle Continuous 100% for 24 hours per day Continuous 100% for 24 hours per day
Efficiency > 85% @ Maximum Output
Environmental Specification
Operating Temp. Range Wide Temperature -40°C to +55°C
Humidity 0 - 95% Relative Humidity
(non-condensing) with optional conformal coating
Audible Noise NONE - Ødb @ 3 ft
Typical Service Life >10 years (87,600 hours)
Isolation Input-Case & input-output 500VDC
Input to Output - Common Negative
Mechanical Specification
Length 18.3 in / 46.6 cm 
Width 5.56 in / 14.12 cm
Height 5.3 in / 13.5 cm
Material Steel
Finish Black Chromate / Powder Epoxy Coat
Fastenings All 18-8 Stainless Steel
Weight 29.5 lb / 13.38 Kg (approximate weight)
Connections 4 – 3/8” Threaded steel stud
Warranty 3 years
Safety Designed to meet CSA 22.2.107.1 & UL458