IVS2000R Series Pure Sinewave DC / AC Inverters
  • front view
NSN# IVS2000R
BENEFITS
  • Ultra-Quiet
  • Power sensitive electronics without interference
  • Rugged & Reliable
  • Ensure years of safe and trouble free operation
Electrical [Input/Output]/ Mechanical Specification
Input Voltage 24V, 32V, 48V, 125V, 270VDC +/-20% are standard
Other inputs available, please consult factory
Input Protection Thermal fuse, Inrush current limiting, Reverse polarity protection
Isolation Input to chassis 500VDC for < 60V input, 1500VDC for > 60V input
Input to output 2250VDC, Output to chassis 2250VDC
Output Voltage 115VAC/60Hz /17.4A continuous with grounded neutral, Isolated floating output optional
Consult factory for other voltages and frequencies
Wave Form Sinusoidal
Total Harmonic Distortion Less than 5% at full load
Efficiency Min. 78% at full load
Line Regulation Max. 0.5%
Load Regulation Max. ± 6% from 10% load to full load
(± 1% option available)
Output Protection Current limiting with short circuit protection, thermal shutdown with
automatic recovery in case of continuous overload or insufficient airflow
EMI Meets EN 55022 Class B
Load Crest Factor Maximum 3.0 at 90% load
Operating Temperature Range 0 °C to +50°C
Humidity 5 - 95% non-condensing
Temperature Drift 0.05% per °C over operating temperature range
Dimensions 3U” X 19” x 15” enclosed case (H x L x W)
Connections Input: Compression-type terminal / Output: Standard AC receptacle
Weight 30.0 lb (13.6 kg)
Safety Compliance to C22.2 No. 107.1 - 01 and UL 458
Options Output Fail Alarm (Form C)
Remote Inhibit: By connecting DC voltage (as specified) to the inhibit terminals
Warranty: Twenty-Four months subject to application within good engineering practice
Enhancements to these general specifications can be accommodated upon request
Designed to meet common approval requirements. Specifications Subject to Change Without Notice
Designed and Manufactured in Canada