Electrical [Input/Output]/ Mechanical Specification
Input Voltage 24V (21-29 VDC) / 48V (42-56VDC) / 125VDC (Operating range 100…150VDC) /
250VDC nominal (Operating range 220…275VDC)
Other inputs available-please consult factory
Input Protection Thermal fuse, Inrush current limiting, Reverse polarity protection
Isolation For 125VDC input version: 2250VDC input to output; 1700VDC input to chassis; 2250VDC output to chassis
For 250VDC input version: 2250VDC input to output; 2400VDC input to chassis; 2250VDC output to chassis
Output Voltage 115Vrms / 34A rms or 220VAC/ 18A (50 or 60Hz standard) with grounded neutral.
Isolated floating output optional (Consult factory for other voltages and frequencies)
Wave Form Sinusoidal
Total Harmonic Distortion Less than 5% at full load
Efficiency Min. 82% at full load
Line Regulation Max. 0.5%
Load Regulation Maximum ± 6% from 10% load to full load ( ± 1% option available)
Output Noise High frequency ripple is better than 500mV rms (20MHz BW)
Output Protection Current limiting with short circuit protection, thermal shutdown with
automatic recovery in case of continuous overload or insufficient airflow
EMI / RFI Suppression Meets requirements of EN55022, Class A conducted emissions as a minimum
Output Over-voltage Protection By internal supply voltage limiting at 140VAC on output
Output Over-load Protection Hiccup at 6,000W
Load Crest Factor Maximum 2.5 at 90% load
Operating Temperature Range 0 °C to +50°C
Humidity 5 - 95% non-condensing
Temperature Drift 0.05% per °C over operating temperature range
Dimensions & Weight 6U x 19” rack-mount enclosure / Depth is 16” maximum / 53 lb (24.1 kg)
Connections Input: Compression-type terminal / Output: Standard AC receptacle
Safety Compliance to C22.2 No. 107.1 - 01 and UL 458
Warranty: Twenty-Four months subject to application within good engineering practice
Enhancements to these general specifications can be accommodated upon request
Designed to meet common approval requirements. Specifications Subject to Change Without Notice
Designed and Manufactured in Canada