LVS1000 Series Sinewave Telecom DC / AC Inverters
  • front view
NSN# LVS1000
BENEFITS
  • Ultra-Quiet
  • Power sensitive electronics without interference
  • Rugged & Reliable
  • Ensure years of safe and trouble free operation
Electrical [Input/Output]/ Mechanical Specification
Input Voltage 24V, 36V, 48V, 125V, 250VDC +/-20% are standard
Other input voltages available
Input Protection Thermal fuse, Inrush current limiting, Reverse polarity protection
Isolation Input to chassis: 1500VDC/ Input to output: 3000VDC/ Output to chassis : 2250VDC
Output Voltage 115VAC / 8.7A continuous or 230VAC / 4.34A continuous at 50, 60 or 400Hz with grounded neutral
Isolated floating output optional / Other outputs available
Wave Form Sinusoidal
Total Harmonic Distortion Less than 5% at full load
Efficiency Min. 78% at full load
Line Regulation Max. 0.5%
Load Regulation Maximum ± 2% from 10% load to full load
Output Protection Current limiting with short circuit protection, thermal shutdown with
automatic recovery in case of continuous overload or insufficient airflow
EMI EN 55022 Class B (typical)
Load Crest Factor Maximum 3.0 at 90% load
Operating Temperature Range 0 °C to +50°C
Humidity 5 - 95% non-condensing
Temperature Drift 0.05% per °C over operating temperature range
Dimensions 2.64” x 19” x 13.97” enclosed case (H x W x L)
Connections Input: Compression-type terminal / Output: Standard AC receptacle
Weight 17.6 lb (8.0 kg)
Safety Designed to meet C22.2 No. 107.1 - 01, UL 458 and EN60950
Options Output Fail Alarm (Form C)
Remote Inhibit: By connecting DC voltage (as specified) to the inhibit terminals
Warranty: Twenty-Four months subject to application within good engineering practice
Enhancements to these general specifications can be accommodated upon request
Designed to meet common approval requirements. Specifications Subject to Change Without Notice
Designed and Manufactured in Canada