IVS3000R Series Pure Sinewave Inverter
Benefits
- Ultra-Quiet
- Power sensitive electronics without interference
- Rugged & Reliable
- Ensure years of safe and trouble free operation
- Download Data Sheet
The IVS3000R Series is a compact 3000VA DC/AC pure sinewave inverter that uses established design techniques to ensure high reliability.
Suitable for a wide range of applications, the IVS3000 features full electronic protection, high efficiency and low output noise.
The built-in fan provides sufficient airflow for operation without de-rating up to 50°C ambient temperature. Extended operating temperature (-40 to +65°C) is available.
Features
- Input is filtered to EN 55022 Class A
- Very low 60Hz input ripple current
- Modular design
- Sinusoidal wave shape
- Multiple input and output voltages available
- 3000VA of output power
- Full electronic protection
- Field-proven design topology
Applications
- Marine / Automotive / RV
- Electric Utilities and Substations
- Telecom Power Plants
- Manufacturing Locations
- Steel Mills
- Military Applications (COTS)
- Industrial Controls
- OEM Applications
- Solar / Alternative Power Systems
- Fuel Cells
| Input Voltage | 24, 32, 48, 125, and 250VDC are standard (Operating range +/-15% of nominal) Other inputs available - please consult factory |
|---|---|
| Input Protection | Thermal fuse, Inrush current limiting, Reverse polarity protection |
| Isolation | 1400VDC input to output, input to chassis / 500VDC output to chassis |
| Output Voltage | 115V rms / 26A rms or 220VAC / 13.6A (50 or 60Hz standard) Consult factory for other voltages and frequencies |
| Wave Form | Sinusoidal |
| Total Harmonic Distortion | Less than 5% at full load |
| Efficiency | Min. 82% at full load |
| Line Regulation | Max. 0.5% |
| Load Regulation | Maximum ± 6% from 10% load to full load ( ± 1% option available) |
| Output Noise | High frequency ripple is better than 500mV rms (20MHz BW) |
| Output Protection | Current limiting with short circuit protection, thermal shutdown with automatic recovery in case of continuous overload or insufficient airflow |
| RFI Suppression | Meets requirements of EN55022, Class A conducted emissions as a minimum |
| Output Over-voltage Protection | By internal supply voltage limiting at 140VAC on output |
| Output Over-load Protection | Hiccup at 6,000W | Load Crest Factor | Maximum 2.5 at 90% load |
| Operating Temperature Range | 0 °C to +50°C |
| Humidity | 5 - 95% non-condensing |
| Temperature Drift | 0.05% per °C over operating temperature range |
| Dimensions | 4U x 19” rack-mount enclosure. Depth is 17” maximum Depending on input |
| Connections | Input: Compression-type terminal / Output: Standard AC receptacle |
| Weight | 55 lb (31.8 Kg) |
| Safety | Compliance to C22.2 No. 107.1 - 01 and UL 458 |
| Warranty: Twenty-Four months subject to application within good engineering practice Enhancements to these general specifications can be accommodated upon request Designed to meet common approval requirements. Specifications Subject to Change Without Notice Designed and Manufactured in Canada |
|