BCD610R Isolated Battery Charger(Ractifier)

Benefits
- Ultra-Quiet
- Power sensitive electronics without interference
- Rugged & Reliable
- Ensure years of safe and trouble free operation
- Fast & Accurate Charging
The model BCD610R Rackmount DC Battery Charger charges either 12V, 24V or 48V batteries from a 110, 220 or 300VDC power source. Other battery voltages up to 360 volts are also available by special order.
The all-new Current Mode switching design offers increased power and reliability in a compact package. Extra input and output filtering reduce EMI to extremely low levels. Reliability features include an input fuse, thermal shutdown, current limiting, reverse battery hookup protection, output short circuit shutdown with automatic recovery, and equalize charging cycle. The output voltage is easily adjusted 1.0 volts above or below the standard output voltage to accommodate special charging requirements.
A high quality Digital Volt/Ammeter allows the monitoring of charging current and charging voltage. We are confident that you will get many years of reliable service from this DC Battery Charger.
Features
- Fully Isolated Design
- Adjustable output voltage for charging standard or deep cycle lead-acid, VRLA or Gel cell type battery
- Extremely rugged and well suited for marine and other demanding environments
- High tolerance for shock and vibration
- Ultra-quiet low EMI operation
- Can be left permanently connected
- Spark free connection
- User selectable 2 or 3 stage charging profile
- Audible & visual indicators for output overload, low input voltage, low output voltage & over-temperature
- Over-temperature shutdown
- Short circuit protection
- Output over-voltage crowbar
- Inrush Current Limiting with solid state bypass
- Dry contact output fail relay
- 3 year parts and labour warranty
Applications
- Marine & other Rugged Environments
- Electric Utilities and Substations
- Manufacturing Plants
- Steel Mills
- Military Applications (COTS)
- Industrial Controls
- OEM Applications
- Solar / Alternative Power Systems
- Fuel Cells
- Charge any DC/DC System
| Nominal Vac (ip) | 110 | 250 | 300 |
|---|---|---|---|
| Actual (Vdc) | 100-140 | 230-280 | 280-360 |
| Input Amps (Max) | 8.2 | 3.6 | 2.9 |
| Input Fuse (MDA) | 10 | 4 | 3 |
| Noise on Input | < 50mV | ||
| Output Nominal (op) | 12 | 24 | 48 |
|---|---|---|---|
| Output Volts (DC) | 13.6 ± 0.05 | 27.2 ± 0.05 | 54.4 ± 0.05 |
| Absorption Voltage (Vdc) | 14.4 | 28.8 | 57.6 |
| Charging Amps | 40 | 22 | 11 |
| Absorption to Float(15%) | 6.0Amps | 3.3Amps | 1.65Amps |
| Output Adjustment(Vdc) | ± 1.0V | ||
| Output Fuses(AGC) | 20Amp x4 | 30Amp x2 | 15Amp x2 |
| Battery Banks | 1 or 2 (Optional 3-bank) | ||
| Battery Size (Amp Hrs.) |
160-240 | 88-132 | 44-66 |
| Output Crowbar | 16.0 ± 0.5V | 32.0 ± 1.0V | 63.9 ± 2.0V |
| Output Ripple & Noise | < 50 mV | ||
| Regulation (Line & Load) |
< +/- 0.5% | ||
| Temperature Comp. | -30 mV/°C | -60 mV/°C | -120 mV/°C |
| Duty Cycle | Continuous 100% for 24 hours per day | ||
| Efficiency | > 75% @ Maximum Output | ||
| Stages | 2 or 3 (user selectable) | ||
| Operating Temp. Range | -25° to +40°C @ maximum output Derate Linearly 2.5% per°C from 40°C (Optional -40°C extra wide temp. operation avail.) |
|---|---|
| Humidity | 0 - 95°C Relative Humidity (non-condensing) with optional conformal coating |
| Audible Noise | NONE - Ødb @ 3 ft |
| Typical Service Life | >10 years (87,600 hours) |
| Isolation | Input-Case & input-output 1500VDC Output - Case 500VDC(1500VDC @ 48V Output) |
| Depth | 13.5 in/ 34.3 cm |
|---|---|
| Width | 19.0 in/ 48.3 cm |
| Height | 2u(3.5 in)/ 8.9 cm |
| Clearance | 1 inch (2.5 cm) all around |
| Material | Marine Grade Aluminium |
| Finish | Black Anodize / Powder Epoxy Coat |
| Fastenings | All 18-8 Stainless Steel |
| Weight | 7.6 lb / 3.3 kg |
| Connections | Four contact output terminals |
| Warranty | 3 years |
| Safety | Approval to cETLus Standards Pending |
Toll Free: 1-800-668-3884
Tel: 604.946.9981
Fax: 604.946.9983
Email Us
Facebook/Twitter/LinkedIn: